EAN 8430892292986
Technical data
Nr. Poles 4
Air thermal rating (Ith) 2000 A
Impulse voltage (Uimp) 12 kV
Minimum Cu busbar cross-section

3x100x5 mm2

Maximum Cu busbar width

100 mm2

Tightening torque 40/45 Nm
Prostpective shortcircuit current (rms) 100 kA
Associated fuse rating 2x1000 A
Rated short-time withstand current 1s (Icw) 50 kA
Standard IEC 60947-3